Transmission And Distribution Of Electrical Energy Set 2

On This Page

This set of Transmission and Distribution of Electrical Energy Multiple Choice Questions & Answers (MCQs) focuses on Transmission And Distribution Of Electrical Energy Set 2

Q1 | The cause of damage to the lead sheath of a cable is
Q2 | The voltage of the single phase supply to residential consumers is
Q3 | Most of the high voltage transmission lines in India are
Q4 | The distributors for residential areas are
Q5 | The conductors of the overhead lines are
Q6 | High voltage transmission lines use
Q7 | Multicore cables generally use
Q8 | Distribution lines in India generally use
Q9 | The material commonly used for insulation in high voltage cables is
Q10 | The loads on distributors systems are generally
Q11 | The power factor of industrial loads is generally
Q12 | Overhead lines generally use
Q13 | In transmission lines the cross-arms are made of
Q14 | The material generally used for armour of high voltage cables is
Q15 | Transmission line insulators are made of
Q16 | The material commonly used for sheaths of underground cables is
Q17 | The minimum clearance between the ground and a 220 kV line is about
Q18 | The spacing between phase conductors of a 220 kV line is approximately equal to
Q19 | Large industrial consumers are supplied electrical energy at
Q20 | In a D.C. 3-wire distribution system, balancer fields are cross-connected in order to
Q21 | In a D.C. 3-wire distributor using balancers and having unequal loads on the two sides
Q22 | Transmitted power remaining the same, if supply voltage of a D.C. 2-wire feeder is increased100 percent, saving in copper is
Q23 | A uniformly-loaded D.C. distributor is fed at both ends with equal voltages. As compared to a similar distributor fed at one end only, the drop at the middle point is
Q24 | As compared to a 2-wire D.C. distributor, a 3-wire distributor with same maximum voltage toearth uses only
Q25 | Which of the following is usually not the generating voltage ?