Refrigeration Test

Automatic expansion valves work with

Evaporator pressure closes valve spring pressure opens valve

A faulty check in a pump will cause the most damage on

Startup

If the T E V's sensing bulb falls off the suction line you will

Flood the evaporator

A clogged condenser pump strainer can cause a loss of pressure causing

High condenser head pressure

A solenoid valve is part of the pump down cycle

Thermostat solenoid valve and then the low pressure control

What is proper start up procedure?

Start chiller water pump, start condenser water pump,check tower fans, check compressor oil, check position of refrigeration valves, start machine.

A reciprocating machine cycles multistage compressors on and off with the

Low pressure control

The refrigerant that has the best refrigerant effect is

Ammonia

In an induced draft cooling tower that is operating efficiently the leaving water temp is at

Some temp between the prevailing dry and wet bulb temp

A sudden reduction in the supply of condenser water could result in

An open valve

Reciprocating compressor unloaders work by

Keeping compression suction valve open

In a well designed system the percent of lubricant circulated should not exceed

10%

Oil foaming in the compressor is a result of

Liquid refrigerant in the crankcase

The main reason for installing a oil separator on the discharge line is to

Return oil back to the compressor crankcase

In a reciprocating compressor using the splash system for lubrication the domain of oil is caused by a

Sudden decrease in pressure

Charge vapor into the

Suction side of the compressor (low side)

Oil in a refrigerant system reduces

Wear and friction

A filter drier is used to

Remove moister

Oil separator is located on the discharge line as

Far from the compressor as possible

A solenoid valve

Does not vary the flow of refrigerant

The T E V

Modulates and controls the flow of refrigerant into the evaporator

If you use an automatic expansion valve with a variable load you will

Starve the evaporator

A motor has 4 belts if one is worn replace

All the belts

Non condensable gases can cause

High head pressure

Horse power will

Increase as the head pressure increases

Horse power will

Decrease as the head pressure decreases

Superheated vapor is defined as a

Dry vapor

A sling psychrometer is used to measure

Relative humidity

An automatic expansion valve maintains a

Constant evaporator pressure

If the evaporator doesn't respond to adjustments of the T E V it may be due

To oil logged on the low side

When using a bribe solution in a system us

Di-chromate tablets to prevent rusting

If a halide torch turns yellow it is caused by

A clogged sample tube

The pressure of having 2 compressors in a cascade system is to operate at

Very low temperatures

A pressure relief valve is better than a fusible plug because a

Fusible plug can not reseat

Compressor knocking could be caused by

Refrigerant slugging in the compressor

If the TEV's spring was to break it would

Flood the evaporator and raise suction pressure

The T E V of equalizer line makes up for the

Pressure drop in the evaporator

When installing pipe and you need a 90 degree elbow use a

Factory made 90 degree elbow and braze it in

A service valve stem cap protects the valve from being

Inadvertently turned from its position and from being damaged

Semi hermetic compressors have the advantage over hermetic compressors because

They can be serviced on site

When using a portable compressor recovery unit to remove vapor the

Vapor density is decreased

The amount of pressure that flows through the orifice plates is determined by the

Difference in pressure between the high and low size

If you were running three compressors the state of refrigerant leaving the third compressor is a

Superheated vapor

A T E V restricts the amount of refrigerant from the

High side to the low side

A halid torch burns from

Blue to dark blue or purple when a week is detected

The main reason for a crankcase breather line is to prevent

Oil from slugging in the compressor

The middle port on a manifold gauges is connected to the

Recovery cylinder or the charging cylinder

A forced draft cooling tower is better then a natural draft because it is

Smaller and not affected by prevailing winds

The proper way to start a pump is to

Open the suction valve and close the discharge valve start the pump and then slowly throttle open the discharge valve (seasonal start up)

Fusible plug setting is

280�

The flashpoint of compressor lube oil is

Higher than the compressor temperature

Heat removed from the refrigerator in the condenser is

Sensible and latent heat

A compressor safety head is a

Valve plate help down by a heavy spring

A centrifugal machine is characterized by

High volume and low pressure

If condenser pressure is high and another pump has to be turned on you would have the

Suction valve completely opened and discharge valve open to a throttled position

If you disconnect the external equalizer on a T E V you would

Flood the evaporator

You achieve capacity control on a reciprocating compressor by

Opening suction valves by using some form of control

The ratio of actual water vapor in the atmosphere to the saturation pressure is called

Relative humidity

The most accurate statement regarding compressor motors that run in a refrigerant atmosphere is that they use

Material tailored to the refrigerant

MUNTZ

Material should not be used with ammonia

Venting a manifold or purge line is prohibited with any

Refrigerant containing chlorine. (HCFC CFC)

You would not use a solenoid valve to

Vary the flow of refrigerant

The muffler is located between the

Compressor in the condenser

Refrigerant affect is always lower than latent heat because

Heat required to cool the refrigerant from compressor discharge to evaporator temperature is subtracted from the latent heat

You use a T E V with an external equalizer when there is more than

2.5 pressure drop through the evaporator coil

Direct systems

Are most likely to week refrigerant into building spaces

Gauges on the high side should be graduated to

At least 1.2 times the design pressure

When brazing in a class T machine room you must in sure the flame is

Enclosed invented to open air

In an emergency you can dump refrigerant under

FDNY supervision

An R-22 system's head pressure with a condenser water supply temperature of 85� is

200-215 p s I g

When you run two pumps in parallel you

Increase total flow rate (GPM) Pressure is the same when running one or two pumps

A refrigerant cylinder can only be filled

75% NYC (a 40 gallon can be filled with 30 gallons)

Calcium chloride sodium chloride and glycol

Are used as chilled water Brines in an indirect system (R-22 is not a brine)

Failure to maintain water temperature of condenser water can result in

High head pressure

Frost on suction line and compressor could be caused by the

T E V being open to wide

If cooling tower is not chemically treated you could cause

Bacteria growth and rusty pipes

The low pressure control

Cycles the compressor on and off

If there is a refrigerant leak the operator should be aware of

Toxicity and oxygen deprivation capabilities of the refrigerant

All group one refrigerants

Require an oxygen deprivation sensor (R-11 R-12, R-22, R-134A)

A low head pressure chiller's ruptured disc is set at

15 p s I

An automatic purge unit is required for systems that operate

Below atmospheric pressure (in a vacuum)

High head pressure and temperature could be caused by

Dirty condensable tubes

If wetbulb temperature decreases it can

Lower the temperature of the cooling tower

Use a three-way valve (service valve)

To isolate the pressure relief valve while keeping the system and service

Charge with the vapor first so you don't

Freeze the evaporator tubes (centripetal machines)

Clogged eliminator fins on a cooling tower could lead to a

Higher condenser supply water temperature

Orifice plates serve as metering devices in centrifugal compresses the vessel they are contained in can also serve as an

Economizer

A jet ejector if restricted will have

Insufficient had to lift the oil (back to the oil sump)

The low side gauge (saturation pressure) can be used to

Estimate to leaving chilled water temperature

Water tube leaks in a low-pressure chiller can be found with

Hydrostatic tube test

R-11 and R-123 refrigerant are

Oxygen depleted, heavier than air and class one and class two substances

A centrifugal chiller purge unit

First takes a combination of air and refrigerant from the top of the condenser then removes air and noncondensible and finally returns liquid refrigerant back to the evaporator

Electric resistant heaters (resister circuit)

Can be used to defrost evaporators

Refrigerant enters the condenser as a

High-pressure gas and leaves as a high-pressure liquid

When using warm water to increase the release the rate of R-12 do not exceed a water temperature of

90�

R-11 water oil at 70� and at atmospheric pressure would settle in a container from top to bottom in this order

Oil on top then water and R-11 on the bottom

You can achieve capacity control on a reciprocating compressor by

Opening suction valves using some form of control (unloaders)

Power consumption from an induction motor is measured in watts using the formula

Volts times amps times power factor

Low condensing pressure is not good because

Expansion valves will not be fed properly

And in-line refrigerant cleaning system (into cleaner) is advisable because

Refrigerant reacts with lube oil

If a condenser water pump is cavitating this problem could be caused by

A faulty water level control

Capacitors our devices which have the ability to

Store electricity and are used to start motors

The refrigerant with the highs latent heat is

Ammonia

Transformers

Areelectric devices which change the value of AC voltage to another AC voltage (step up or step down voltage)

The most common metering device used on reciprocating commercial systems under 3 tons is the

Thermostatic expansion valve (also used over 3 tons)

The maximum pressure used to leak test low-pressure chillers is

10 P S I G

Under the EPA regulations you can pressurize the system for a

Non-major repair with nitrogen and a trace of R22

Under EPA regulations replacement of an

Evaporator coil is always considered a major repair

R11 at 14.7 p s I a (0 p s I g) will boil at approximately

74.5�

When you remove valve plates you should replace

The valve plate and the valves

If an electric motor has its windings reduced by one half and all other factors remain equal the power developed by the motor is

Decrease by one half

If a system is excessively cycling crank case temperature is high, discharge is low, and suction is high this could be caused by

Faulty compressor valves

Centrifugal compressors can control capacity with

Variable inlet guide veins

Centrifugal compressors can control capacity with

Variable speed motors

On a reciprocating compressor there are stop valves on the

Inlet (suction side) and the outlet (discharge side)

To prevent freezing water coils of a low-pressure chiller you should first

Charge as a vapor; circulate water, do not charge liquid until the saturation temperature is above 38�

Refrigerant is added to a low-pressure centrifugal chiller through the

Evaporator charging valve

You can store anextra 20% of refrigerant charge up to a maximum of

300 pounds on site

Before a low-pressure appliance is dismantled and salvaged

Refrigerate must be recovered

Compound gauges measure

Positive pressure and negative pressure (vacuum)

Oil traps or oil separators return or oil back to the

Compress crankcase

If a motor goes off on overload you could check it's amperage with an

Ammeter

You can check a short in a compressor motor with an

Ohmmeter

If you pump down a compressor to 25" HG then stop the compressor. If the pressure then increases you could have

Faulty compressor valves

The pressure a centrifugal compressor can develop depends on the

Top speed of the impala

If the external equalizer was to break you would lose

The entire charge

Oil pressure should be at least

15 to 30 p s I g above the suction pressure in a reciprocating compressor

Shell and coil condensers are not mechanically serviceable and must be cleaned

Chemically

Shell and tube condensers can be

Mechanically clean with brushes

To minimize pressure drop

Avoid using a globe valve

A condenser pump in the basement has 120 p s I g at the inlet from the basement to the roof cooling tower the height of water is 277 feet what is the formula

2.3 1 times 120 = 277 .2

Glycol is better than brine because it

Eliminates corrosion problems

Water regulating valves work off of

Condenser head pressure

Refrigerate enters the compressor as a

Low-pressure superheated vapor and leaves as a high-pressure superheated vapor

Suction pressure increases

The refrigerant affect per ton decreases

T E V sensing bulb is attached on the suction line at the

End of the evaporator

Outdoor cooling towers have this to prevent freezing

Heating coils

The low side flow controls the

Low refrigerant into the evaporator

In a refrigeration system the heat absorbed in the evaporator is later rejected in the cooling tower using the process of

Evaporation

An older type of cylinder unloader is designed to control

Cylinder clearance pockets

A fast way to check gauge pressure reading in the field is to

Open it to atmospheric pressure it should read 0 p s I g

If the suction pressure is 62 p s I g and discharge pressure is 110 p s I g the compression ratio is 1.6 the formula is

Discharge pressure p s I a divided by the suction pressure p s I a (add 14.7 to convert psig to psia ) 124.7�76.7

If a unit using a low side float was short cycling it could need

Additional refrigerant to be charged

If a hot wire is touching the inside of the motor casing a R M O could get an

Electric shock if touched

If a centrifugal pump is running fine at full discharge but if throttled it loses flow

A clogged strainer could be the cause

A fusible plug would not be used in a system that

Does not have any heat

A Compressor stuffing box prevents the

Leaking of refrigerant vapor

The A E V works on two pressures

Evaporator pressure is closing force and spring pressure is the opening force

If you overcharge the system you will run with

High head pressure

An evaporative condenser uses both

Air and water

Silver solder

Is used to connect to pipes together when brazing

If there is a 5 pound pressure drop in the evaporator the external equalizer line will supply a

Closing pressure to the T E V from the same point the temperature of the sensing bulb is taken

Copper piping is used in refrigerant because it is

Good conductor for heat transfer

High-pressure vapor is found

Above the compressors valve plate

Low-pressure vapor is found

Below the compressors valve plate

Oil collected in the oil separator is generally returned

Back to the compressor crank case

Automatic water regulating valve is very water flow according to

Condenser head pressure

If they are R M O needs to vary flow of refrigerant in a system where the continuous variation in flow

Does not include the solenoid valve

If high superheat appears in the suction line this could indicate you are

Low on refrigerant

You would not use a fusible plug on a system with no temperature because it releases on

High temperature only and not on high-pressure

If the compressor failed to start and you already checked the electric circuits motors, switches, and breakers the problem could be a

Faulty pressure temperature control (low pressure controller)

The advantages of an A E V is it

Maintains a constant evaporator pressure, it's a simple design and little could go wrong, and an excessive charge will have no effect

You find stop valves (service valves) on the

Inlet of the compressor and the discharge of the compressor and on the outlet of the condenser or receiver

The T E V drops refrigerant from a high-pressure liquid to a low-pressure liquid it also

Maintains a constant superheat in the evaporator

You would use copper and aluminum tubes because of their

Thermal characteristics for transferring heat

Imprinted on the fusible plug is the

Temperature at which it melts

If a machine with a R - 123 had a leak the

Refrigerant monitor would go off

When a purge unit is running the

Compressor must also be running

Another disadvantage of the A E V besides not responding well to various loads is that it

Does not work well with more than one evaporator in the system

The solenoid valve has a magnetic coil that

When energize will lift a plunger off the seat (normally closed valve)

Liquid line solenoid valves are sized according to

Refrigerant tonnage and a pressure dropped to the valve that is acceptable

Low pressure chillers should not be pressurized above

10 psig or you could blow the rupture disc

Pressure relief devices discharge point must be

15 feet above the ground and must be 20 feet or more from any window vent opening or building exit

If city water is too expensive if available water from

Well, rivers, lakes, or the ocean may be used

Fusible plugs give no protection against

Excessive pressure developed by other means than heat

The refrigerator inside the T E V's sensing bulb is known as the charge for the T E V. There are four types of charges that could come with the T E V. They are

Liquid charge bulb - cross liquid charge - vapor charge bulb - cross vapor charge bulb

Liquid cross charge and vapor cross charge have

A different charge in sensing bulb then the system charge

The restriction caused by filter dryer in the suction line can cause

More reduction in capacity then a filter dryer in the liquid line

Air, nitrogen, and other noncondensible gases collect in the

Condenser

Activated ammonia, silica gel, and drierite

Are frequently used as desiccants in filter driers

Ammonia system sight glasses are the liquid glass type and have

Automatic check valves and manual had valve in each line to the glass

Wearing rings prevent discharge water from leaking back into the suction I of the impeller this leakage could cause

Damage to the impeller and the pump casing

Flare connections are not used on copper tubing larger than three quarters of an inch. It is

Too hard to tighten sufficiently to make a gas tight joint in larger sizes

Compression valves are located on

Both sides of the valve plate discharge on top and suction below

In the winter air cooled condenser's can be controlled by

Cycling fans - variable speed motors or damper controls

The water regulating valve opens or closes automatically in response to the condensing pressure and

Maintains the set or desired condensing pressure

Cooling towers require chemicals to

Reduce the formation of scale and algae

When testing a three-phase circuit with the clamp on type Ammeter

Check each phase individually

A centrifugal pump is fully primed when it is

Full of liquid and all the air has been removed

A strong wind could cause

A problem when using a halide torch on the roof

Synchronous motors run with a

Leading field current

The amount of ventilation for refrigerant removal purposes should be determined by the refrigerant content of the

Largest system in the machinery room

Each fusible plug must be marked with the

Melting temperature of the alloy

Recovery cylinders are

Gray with yellow tops

A low refrigerant charge will

Starve of the evaporator

The petcock on a pump is used to

Bleed air from the pump

Filter driers use a

Desiccant to remove moisture

Superheat

Dry vapor above its boiling point

A efficient condenser runs with

A low condenser pressure

The order of devices in the liquid line is as follows:

King valve, filter drier, solenoid valve, sight glass, T E V