NATE Air Distribution

What is the function of a transformer in a gas furnace?

It reduces line voltage to control voltage.

On a call for heat, the thermostat energizes the __________ terminal

W

What is the function of the inducer in a gas furnace?

It brings in air for combustion

Rollout limit switches are located in the __________.

Burner area

Which of the following statements is true regarding inshot burners?

They require a seperate flame carryover channel.

A furnace with an AFUE of 90% or higher has ___________.

Both primary and secondary heat exchangers.

For natural gas applications, an ideal line pressure is __________

7.0 in. w.g.

For natural gas applications, the manifold pressure typically is set at _____________.

3.5 in. wg.

In a gas furnace application, "ESP" refers to the ___________.

resistance to air flow in the supply and return ducts

What is the first step in the sequence of operation for a typical gas ignition system?

The thermostat closes the R-W circuit

In a counterflow furnace, air passes from ___________.

The top to the bottom of the furnace

Regarding combustion air requirements, a "confined space" is defined as a space who's volume is ___________ per 1,000 BTUH of the combined input rating of all appliances installed in that space.

Less than 50 ft.^3

Oil furnaces are vented with _________ venting material.

Type L

The purpose of a CAD cell in an oil furnace is to _______________.

Prove the presence of flame

Normal CAD cell resistance is ______________ with flame present.

Less than 1,600 Ohms

Oil furnaces typically are designed to burn _____________.

#2 fuel oil only

Why is it necessary to bleed fuel lines prior to burner operation?

To remove air bubbles.

What tools are used to adjust an oil burner?

CO2 analyzer and smoke gun.

A properly adjusted oil burner should have a smoke test reading of _________.

0

Net stack temperature should be within the range of _____________

400 to 500 *F

If the measured temperature rise is ___________ than the range shown on the furnace rating plate, you should __________ the blower speed.

Higher, increase

Air flow should be as close as possible to _________ per ton of air conditioning.

400 CFM

The compressor changes refrigerant from a ________ to a _________.

Low-pressure vapor, high-pressure vapor

In the condenser, refrigerant is changed from a _________ to a _________.

High-pressure vapor, high-pressure liquid

The purpose of a metering device is to __________.

Create a pressure drop

A system that uses a TEV as a metering device _____________.

Must be charged by the subcooling method

What is the state of the refrigerant leaving the evaporator?

Low-pressure vapor

When you use the superheat method of verifying a system's refrigerant charge, adding refrigerant should ____________.

Increase suction pressure and decrease suction temperature

When you use the subcooling method of verifying a system's refrigerant charge, what should you do if the measured subcooling is more than 3 *F lower than the recommended subcooling value?

Add refrigerant in the vapor state.

Many "no cooling" calls are due to ________.

Neglected air filters

What type of refrigerant oil must be used with R-410A?

POE

Which thermostat terminal controls the reversing valve if the manufacturer energizes the reversing valve in the heating mode.

B terminal

Terminal "R" on a thermostat is used for ____________

24-V ac input

Thermostats that have W2 and/ or T2 terminals are known as ____________

Multistage

In general, the "O" terminal on a heat pump thermostat is energized whenever the system selector switch is set to _______

Cool

The purpose of a heat anticipator is to __________

prevent wide swings in room temperature.

A bimetallic strip is a(n) _________ control

Electromechanical

Fossil-fuel kits often are used in ____________ systems

Heat pump

Low-ambient controls are used to ______________.

Maintain high-side pressure when the outdoor temperature is low

A bypass damper is a component of a(n) ____________ system

Zoning

Enthrall controllers measure ________________.

Both dry-bulb temperature and humidity

PTC and NTC thermistors are often used as ____________.

Sensors

For rectangular sheet metal ducts, the usual duct depth is ____________.

8 in.

Which duct system component connects a stack to a horizontal duct at a lower level?

Boot

Which duct system component delivers air to a register box?

Branch duct

A standard elbow has a curve ratio of ___________.

0.5

Take-offs should be placed at least ________ duct diameters or elbow widths downstream from an elbow.

7 1/2

A fire damper is activated with a ___________.

Fusible link

For heating application, local air velocities generally are ____________.

Less than 40 ft/min

The distance traveled by an airstream between leaving the discharge outlet and the point at which its velocity falls below some specified terminal level is called the __________.

Throw

How many air changes per hour are required to prevent the formation of stagnant regions of air?

8 to 10

For cooling operation, what is the ideal location for a return intake?

Near the ceiling

Lengths of round duct may be joined by using any of the following except _______________.

Drive clips

The radius of a flexible duct bend must not be less than the ________ of the duct.

Diameter

When run horizontally, flexible duct must be supported at maximum intervals of _____________.

5 ft.

When run vertically, flexible duct must be supported every __________.

6 ft.

Flexible duct sag should be limited to _______ per linear foot between supports.

1/2 in.

Which of the following is not approved for sealing duct board?

Duct tape

What technology provides for multiple temperature-controlled areas within a structure?

Zoning

The exchange of indoor air for outdoor air is known as ____________

Ventilating

Which of the following devices can provide "free cooling" when outdoor conditions permit?

Air-side economizer

A differential enthalpy controller measures _____________.

Both dry-bulb and wet-bulb temperatures

In a forced-air system, static pressure is a force that ____________.

Pushes against the walls of a duct from inside the duct.

Gauge pressure plus atmospheric pressure equals _________ pressure

Absolute

In a forced-air system, velocity pressure is the ________________.

Difference between the total pressure and the static pressure.

The process of measuring velocity pressure at several locations across a cross section of duct is knows as making _____________ reading.

Traverse

Which of the following test instruments provides direct readings in feet per minute?

Anemometer

In any duct system, when the velocity of air is _______, the resistance to air flow is _______________.

Increased, increased

Which of the following is not a factor in determining proper duct size?

Temperature difference

In a duct system, the angle between the sides of a transformation piece (from larger to smaller must be less than _____________.

60*

Which equation is used to calculate the rpm of a belt-driven fan?

Motor pully diameter X motor rpm / fan pulley diameter

What is the synchronous speed of an AC induction motor that has six poles and operates with a 60-Hz power supply?

1,200 rpm

The CFM of a fan is ________ the rpm of the fan.

Directly proportional to

Static pressure is ____________ the rpm of the fan.

Proportional to the square of

The efficiency of a fan is defined as its ____________ divided by its __________

Power output, power input

Humidity often needs to be added to the conditioned air in the __________ mode.

Heating

Humidity often needs to be removed from the conditioned air in the _______________ mode.

Cooling

The external static pressure (ESP) of a system is measured in __________

In. w.g.

Depending on the manufacturer, a heat pump application that requires 6 ton of cooling will have a total system air flow requirement of approximately ________________ CFM.

2,700 to 3,000 cfm

In high latent heat applications, how should the fan speed be adjusted to increase dehumidification?

Fan speed should be decreased.

In high sensible heat application, how should the air flow rate be adjusted to avoid unwanted dehumidification?

Air flow rate should be increased.

In a balanced air distribution system, the total supply CFM should be __________ the total return CFM.

Within +- 10% of

A common recommended air flow for residential cooling applications is __________ per ton of cooling.

400 cfm

What effect does reducing the cooling blower speed have on the temperature drop across the evaporator coil?

The temperature drops will increase.

Excessive humidity in the conditioned space may indicate that the _________________.

Blower speed is set too high

What effect does high ESP have in the heating mode?

Higher-than-normal temperature rise.

ESP often is measured with a(n) _______________.

Magnehelic gauge

What is the first step in investigating a "noisy equipment" complaint?

Gather as much information as possible from the customer.