608 Core 2

R123

HCFC

CFC's were no longer manufactored or imported into the US after

1995

When using nitrogen to pressurize a system you should always?

charge through a pressure regulator

The EPA requires the installation of a service repair aperture or process stub on all appliances using s class 1 or 2 substance as a refrigerant. the main purpose is to make it easier to

recover refrigerant

R500

CFC

It has been illegal to vent subsistutes for CFC and HCFC refrigerants since

November 1995

Synthetic lubricant presently used with tenerary blends containing HCFC is

alkylbenzene

Refrigerant enters the exspansion or throttling device is a

liquid

R410A

HFC

R22

HCFC

Refrigerant leaves the system as a

high pressure liquid

In a refrigeration system the device that changes a low pressure vapor to a high pressure vapor is the

compressor

Ozone Depletion potential is

a measure of the abilit of CFC's & HCFC's to destroy the ozone

In a refrigeration system, high pressure vapor is converted to high pressure liquid in the

condenser

R13

is a "very high pressure refrigerant" under EPA regulations

A hermetic compressor must never be operated when

there is a dehydration vacuum in the system

Recovery equipment that relies upopn the pressure of the refrigerant in the appliance would be considered

System-Dependent

ozone in the stratosphere above the earth consists of

molecules of 3 oxygen atoms

Azeotropic refrigerant mixture can

act like a single-component refrigerant over its entire range

Refrigerant that enters the compressor under normal operating condidtions is a

low pressure liquid

R12

CFC

ester based oils can be mixed with

no other oils

R134a

HFC

Self contained recovery devices

has its own means of drawing refrigerant out of the system and is capable of removing the refrigerant (liquid and/or vapor) from an appliance without the assistance

The evaporation temperature of R134a at )psig is

-15F

The EPA regulations requires that any appliances containing more than 50 pounds of refrigerant must be repaired when the leak rate exceeds_____ of the charge per year

15%

CFC's will no longer be manufactured or imported to the US after

1995

Recovery equpiment used for the service or repair of small appliances must be certified by an EPA approved lab if the recovery equipment was made after

Novemnber 1993

Recovery devices that were manufactured after November 1993 and are used for recovery of refrigerant from small appliances must be capable of

recovering 90% of the refrigerant when the compressor is operating or achieving a 4" vacuum under the conditions of ARI-740-1993

When ever nitrogen is used to pressurize or blow debris out of the system, the nitrogen

can be vented

A passive system-dependent recovery device for a small appliance

captures refrigerant in a non-pressurized container

According to the EPA which recovery equipment maintenance practices should be preformed on a regular basis?

check recovery tank for refrigerant leaks

A standard vacuum pump designed specifically for evacuatiopn and dehydration can

never be used as a recovery device in combination with pressurized container

Heat pumps that use R134a should be leaked checked with

pressurized nitrogen

The EPA regulations require that any appliances containing more than 50lbs of refrigerant must be repaired when the leak rate exceeds____ of the charge per year

15%

Recovered refrigerant may contain

oils, moisture, acids

Refrigerant should be removed from the condenser outlet if the

condenser is below the reciever

R11, R12

CFC

R410A requires recovery tanks rated for at least

400psig

After refrigerant liquid has been removed from a system any reamaining vapor is

condensed by the recovery system

R410A requires a high pressure manifold gauge and hose set. They must have a

4000psig burst pressure and 800psig working pressure

To change the compressor on a system containing 40lbs of R500, using a recycling machine the was made after 11-15-93 you must isolate the compressor then

Evacuate the isolated section of the system to 10" of the vacuum and hold. If system pressure does not rise, remove the compressor

A system can be evacuated to only atmospheric pressure when

leaks in the system make evacuation to prescribed level unattainable

When using recovery or recycling equipment that was made after 11-15-93 you must evacuate a system containing more than 200lbs of CFC-12 to ____ before making a major repair

15 inches if HG vacuum

Noncondensables in a system cause a

higher discharge pressure

When charging an R410A system that uses a water cooled condenser you must first charge with vapor to a pressure of at least

120psig before switching to liquid charging

Oil foaming usally occurs in the

compressor

When charging an R12 refrigeration system that uses a water-cooled condenser, you must first charge with vapor to a pressure of at least

35 psig before switching to liquid charging

Every air conditioning or refrigeration should be protected by a

pressure relief device

According to ASHRAE guideline 3-1996 if the pressure in a system rises from 1mm Hg to a level above

2.5 mm Hg during a standing vacuum test the system should be checked for leaks

A typical setting for the high pressure cut out control on a recovery unit used for evacuating the refrigerant from a low pressure chiller is

10 psig

To determine how much vapor to charge into an evacuated chiller you should charge with vapor until

the system pressure corresponds to a refrigerant saturation tempature of 36F

refrigerant 11 at 14.7 psia will boil about

74.5F